בהתאם לתקני
DIN VDE 0262, DINVDE 0263, DIN VDE 0265, DIN VDE 0266, DIN VDE 0267, DIN VDE 0271, DIN VDE 0273 ,DIN VDE 0276 part 603, 604, 620, 622, 626
הקודים לבחירת כבל מרכיבים את המקט הכללי, כאשר בוחרים את סוג הבידוד, מרכיב המוליך וצורתו
לקוח מאתר לינק קובץ להדפסהType Designation Codes _ Bayka
דוגמה למק"ט כבל כדי לזהות את הפרמטרים
NYCWY 3 x 120 SM/70 0,6/1 kV
NA2YSEY3 x 70 SE/16 5,8/10 kV
בידוד:
| CODE | DESCRIPTION |
| (F) | Longitudinally watertight cable (screen) |
| 1Y | Outer sheath of polyurethane (PUR) |
| 2X | Insulation of cross-linked polyethylene (XLPE) |
| 2Y | Insulation of thermoplastic polyethylene (PE) |
| 2Y | Outer sheath of polyethylene (PE) |
| A | Aluminum conductor |
| B | Steel tape armouring |
| C | Concentric conductor of copper |
| CE | Concentric conductor in multi-core cables on each individual core |
| CW | Concentric conductor of copper, waveform (ceander) |
| F | Overhead line cable (DIN VDE 0276) |
| F | Armouring of galvanized fl at steel wire |
| FE | insulation sustaining |
| G | Helix of galvanized steel tape |
| H | Field limiting conductive layers over the conductor and over the Insulation |
| HX | Insulation of cross-linked halogen-free polymer blend |
| HX | Sheath of cross-linked halogen-free polymer blend |
| N | Cables acc. to standard |
| R | Armouring of galvanized round steel wires |
| S | Braided copper |
| SE | For multicore cables fileld limiting conductive layers over the conductor and the insulation and copper screen over each individual core (indicated by “H” is omitted here) |
| X | Insulation of cross-linked polyvinyl chloride (XPVC) |
| Y | Insulation of polyvinyl chloride (PVC) |
| Y | Inner sheath of polyvinylchloride (PVC) |
| Y | Outer sheath of polyvinylchloride (PVC) |
שטח חתך, מבנה וצורה:
| CODE | DESCRIPTION |
| E | Solid conductor |
| H | Waveguide |
| M | Stranded conductor |
| OM | Oval shaped conductor, stranded |
| R | Circular conductor |
| RE | Circular conductor, solid |
| RM | Circular conductor, stranded |
| S | Sector shaped conductor |
| SE | Sector shaped conductor, solid |
| SM | Sector shaped conductor, stranded |
| V/ | Compacted conductor |
כבל עם בידוד
בהתאם לתקני:
DIN VDE 0256, DIN VDE 0257, DIN VDE 0258 and DIN VDE 0276 Teil 621
| CODE | DESCRIPTION |
| 2Y | Protective sheath made of Polyethylene (PE) |
| A | Aluminum conductor |
| A | Protective sheath and outer sheath made of fibrous material |
| AA | Double outer protective sheath of fibrous materials or fiberglass tape |
| B | Steel tape armouring |
| D | Bandage protection (only DIN VDE 0256) |
| D | Non-magnetic bandage protection (only DIN VDE 0257) |
| E | Cores with Individual metal sheath and corrosion protection |
| E | Protective sheath with embedded layer (eg wrapping) of elastomer or plastic tape (not DIN VDE0257) |
| F | Armouring made of fl at steel wires with counter or helix, which is removed before the pulling ofa cable into a steel pipe (only DIN VDE 0257 and DIN VDE 0258) |
| F | Armouring made of fl at steel wires |
| FO | Armouring made of fl at steel wires, open |
| GB | Counter helix (metal tape) |
| H | Shielding (H-type cable) |
| K | Lead sheath |
| KL | Pressed aluminum sheath |
| KLD | Pressed aluminum sheath with strain elements |
| N | Cables acc. to standard |
| R | Armouring made of round steel wires |
| RO | Bewehrung aus Stahlrunddraht, offen |
| St | Steel pipe(only DIN VDE 0257 und DIN VDE 0258) |
| u | Non-magnetic (only DIN VDE 0256) |
| u | Cables not stranded (only DIN VDE 0257 and DIN VDE 0258) |
| v | Stranded cable (only DIN VDE 0257 aund DIN VDE 0258) |
| Y | Protective sheath made of polyvinylchloride (PVC) |
| Z | Armouring of Z-shaped steel profi le wire |